electrical appliances

LEADER DC MCB 80-125 A

LEADER DC miniature circuit breakers with thermo-magnetic tripping for overcurrent and short-circuit protection. DC voltage ratings depend on pole configuration.

Share

Key Advantages

Thermo-magnetic protection; multiple pole and current options; contact position indicator; cable, pin-busbar and fork-busbar connections; 35 mm DIN-rail installation.

Core Specifications

Standard: IEC/EN60947-2

Protection: Overcurrent and short circuit

Trip type: Thermo-magnetic

Poles: 1P / 2P / 4P

Rated current In: 80, 100, 125 A

Rated voltage Ue: 1P: 250 VDC; 2P: 500 VDC; 4P: 1000 VDC

Rated breaking capacity: 6000 A

Impulse withstand voltage Uimp: 4000 V

Power-frequency withstand test: 3 kV / 1 min

Thermal release: (1.05-1.30) × In

Magnetic release: (8-12) × In

Electrical/mechanical life: 4000 / 10000 cycles

Contact position indication: Yes

Protection degree: IP20

Ambient temperature/max. humidity: -5°C to +40°C / 95%

Terminal connection: Cable / pin-type busbar / fork-type busbar

Max. cable terminal size: 35 mm²

Max. tightening torque: 2.5 N·m

Installation: 35 mm DIN rail

Applications

Overcurrent and short-circuit protection in DC distribution circuits.